Features
- Loops: 1 (DMTech protocol)
- Devices per loop: 250
- Maximum resistance of a loop – 100 Ohm
- Maximum consumption of a loop – 500mA
- Connecting line – two-wire shielded
- Conventional line 1: (Up to 32 conventional fire detectors)
- Zones: 8
- Outputs (monitored, relay type): 2
- Outputs (non monitored, programmable, relay type): 3
- Output for fault conditions( relay type, C/NC/NO): 1
- Memory LOG: 1024 events
- Display: 4*20 symbols LCD
- Multi language support: Yes
- Programming: DMTech software
- Standard: EN54 – 2/4
- Interfaces for communication with external devices – RS485 and USB.
- Back-up Power Supply – 2 x 12V DC / Capacity C20 (4.5 or 5)Ah
- Electrical output : (24±3.6)V / 2А
- Main Power Supply 90 ÷ 264 VAC / 50 ÷ 60 Hz
- Operating temperature minus 10°C to +40°C
- Dimensions: 305 x 250 x 95 mm
- Weight (without battery): 1.2kg
Category: DMTech Fire Alarm